How it works

States

State LEDs
LEARN green blinking First 60 s, building the humidity baseline. Fast, even blink
IDLE, VOC still settling green, one slow flash Humidity is done. The odor pixel has not gone flat yet: one 400 ms flash every 2.4 s. Light and humidity still run the fan
IDLE green solid Fan off, and the odor pixel has settled — or there is no odor sensor
RUN red solid Fan on — light, humidity and/or odor
BOOST red blinking 15-minute manual override
FAULT alternating Sensor silent, or fan commanded on but not turning
button held 2 s both solid Let go now and it relearns
button held 8 s both blinking together Let go now and the WiFi window opens
WiFi window open green double-blink Waiting for a password — see “Setting up a unit”

Short button press boosts for 15 minutes, or clears a fault.

Hold two seconds to relearn every baseline — humidity, odor and NOx — then let go. Both LEDs come on solid the moment the gesture is long enough, so you can feel for it rather than count; keep holding and they start flashing together instead, which is the WiFi window and not what you wanted. The green blink that follows is LEARN, reseeding from the air the room has now.

This is the one control that needs no app and no network, and it is the right one to reach for after moving the unit, after a power cut that reseeded a baseline mid-event, or whenever the fan is running on air that smells of nothing.

Control logic

  • Baselines update only while IDLE, dark, dry and with the odor path quiet, so neither a shower nor a smell can teach the controller that it is normal. The odor baseline additionally waits for its own pixel to settle, and a refusal to learn expires after VOC_HOLD_MAX_S — otherwise a baseline that is simply wrong could never correct itself.
  • Fan starts on light-on, at RH_RISE_ON (+8 %) above baseline, or at VOC_RISE_ON ticks of odor deviation — the last of which is 0, meaning off, until you set it.
  • After the light goes out it keeps running until humidity falls within RH_FALL_OFF (+3 %) of baseline and the odor has cleared to VOC_FALL_OFF.
  • A humid spell suppresses odor triggering for VOC_RECOVER_S afterwards: drying a wet room moves the gas signal on its own, and that is not a second reason to run.
  • Bounded by a 5-minute minimum (MIN_RUN_S), a 2-minute post-light minimum and a 45-minute hard stop.
  • A stall fault latches, counts to 3, and backs off 5 minutes between retries — it does not clear just because the humidity sensor is healthy.
  • Hitting MAX_RUN_S latches. Without that the cap protects nothing: idle re-reads the same humidity, finds it still above the trigger, and starts another full run seconds later. The latch clears when the room actually dries, when the light comes back on, or on a boost or relearn — and, if odor alone is holding it, after VOC_REST_S, because an odor source can stop at any moment and sitting out the event helps nobody.
  • why on the dashboard names every reason that currently applies and is recomputed each pass, not frozen at whatever started the run.

What a real shower looks like

Measured in the room, 40 mm fan:

Baseline 53.1 %
Peak 91.6 % RH, +38.5 % above baseline, four minutes in
Fast phase −5 %/min while airborne steam clears
Slow phase −1 %/min, then −0.5 %/min as surfaces evaporate
Plateau 68–69 %, about +15 %, and it stops falling

The plateau is the finding — but it is not permanent. Left alone the room does come back: it was measured at +2.1 % later the same evening, inside RH_FALL_OFF. So the drying logic works; it simply needs longer than half an hour, which is why MAX_RUN_S moved from 30 to 45 minutes rather than the stop condition being loosened.

That is not a tuning problem. A 0.25 W, 40 mm fan stirs air; it does not extract it. The number to design phase 3 against: pull the room from 91 % back under 56 % within 30 minutes.

Commissioned values

Measured on the built hardware:

Fan 4,080–4,206 rpm (rated 4,500 at a true 5 V)
DHT22 25.0 °C, 52.3 %RH, 3/3 reads
Stall margin 5.1× over MIN_RPM
Fan pin at boot 0 — the base pulldown holds it off before code runs
Light, bathroom dark 4,800–6,225 raw
Light, bathroom lit 30,000–32,500 raw
Autonomous run dark → LEARN → IDLE → light → RUN → fan at 4,013 rpm

The last row is the whole thing working unattended: it learned a baseline in the dark, idled, saw the light come on, started the fan, and the tachometer confirmed it. No button, no command.

A note on the transistor

If the fan runs when the base is low and stops when it's driven high, the part is a PNP. S8050 (NPN) and S8550 (PNP) are complementary parts in identical TO-92 packages with near-identical markings, and kits mix them. Diode-test it before fitting: red probe on the middle leg should read ~0.7 V to both outer legs. Black-on-middle reading 0.7 instead means PNP, and it will never work here in any orientation.

A PNP in this socket also sits with its base-emitter junction reverse-biased near 5 V against a 6 V limit, which destroys it. That cost two parts and most of an evening. troubleshoot.html covers the full test.