A bathroom extractor fan controller on a Raspberry Pi Pico 2 W. It turns the fan on for light, humidity and odor, runs it until the room is dry, and talks to Home Assistant, or to nothing at all.

Mains voltage

The V2 build in hardware/v2/ connects to mains voltage. Mains wiring can kill you and can start a fire. Build it only if you are competent to work on mains, keep it unplugged while it is open, and follow your local electrical code, which may require a licensed electrician for a fixed ceiling installation. The V2 board has not been fabricated or tested yet. It is a design to check, not a proven build. The V1 build runs on 5 V USB and has no mains anywhere. This project comes with no warranty (see the license).

New here? Try the live demo of the app, then build your own.

Page What's in it
Build your own Parts, wiring, pin map, first install
Set up a unit Wi-Fi provisioning, naming, calibration
Networking and Home Assistant The fan's own server, MQTT, the dashboard
Updating over the air Signed OTA, and why it cannot brick the board
How it works States, control logic, a real shower
Odor sensing The SGP41 and its sign

Why baselines, not thresholds

A humidity-, odor- and occupancy-driven extractor fan controller. The room light is the occupancy signal; humidity decides how long the fan keeps running after the room empties; a gas sensor catches the thing neither of those notices.

Absolute humidity thresholds don't work for this — a muggy August day sits at 65 %RH by itself and the fan never stops. So everything is expressed as a rise above a slowly learned baseline for that particular room.

Absolute light thresholds don't work either, for the same reason and more sharply. Measured here, direct sun reaches 85 % of the ADC's range while the ceiling fixture reads 81 %: daylight is brighter than the bulb, so no level separates them, and the fan ran 175 minutes in a dry room on sunlight alone before this was understood. What does separate them is speed — the fixture moves the reading 51511 counts in a single 2 s sample, and the fastest the sky has ever managed in this room is 51. So the light is found by the step away from a learned ambient, never by a level, and light alone stops holding the fan on after LIGHT_ONLY_MAX_S. Details and the measurements are in config.py.

Absolute odor thresholds don't work either, and this one is the hardest of the three. The SGP41's two pixels report raw tick counts with no absolute meaning — the number depends on the element, its age, the room and how long it has been powered — so once again the fan acts on a deviation from a learned baseline, and note the sign: the signal falls as the air gets worse. Two measurements are worth carrying before trusting it. Both pixels track room humidity hard enough that 0.3 °C of overnight cooling moves the odor channel by its entire trigger threshold. And the element settles far more slowly than a timer suggests — about 30 minutes for the VOC pixel and about two hours for NOx, measured over a 9.2 h overnight series — so a baseline is seeded only once that pixel's raw count has actually stopped moving, per pixel, never on a stopwatch.

Nothing acts on the NOx pixel. It is recorded so that odor-with-NOx (a gas flame in the kitchen) can one day be told from odor alone (the bathroom), but its quiet-room wander is larger than any threshold worth setting, so it drives nothing today.

Odor triggering ships off — VOC_RISE_ON = 0. The sensor reads, records and publishes from the first boot; you set a threshold once you have watched your own room for a few days. Humidity and light work regardless.

Status: running on hardware and commissioned. Three sensing paths — humidity, light and odor — plus fan switching, both status LEDs, the button and the tachometer, all verified on the board. Over-the-air updates install and hold as of 2026-11-03. Parked work is on the roadmap.